The RPC-03-A is a proportional controller designed for actuators, consisting of a 12-bit A/D converter and an 8-bit microprocessor. It compares input signals with the actuator's position to drive OPEN and CLOSE contacts and outputs the current position value.
The manual provides detailed instructions on configuring input signals, setting dead bands and delay times, performing automatic settings, and maintaining the device to ensure long-term operational stability. This manual is written in Chinese.
| Power Supply | 110/220V AC ±10% 50/60HZ ±2% 4VA MAX |
|---|---|
| Input Signals | 4~20mADC, 1~5vVDC, 2~10VDC, 0~5VDC, 0~10VDC |
| Output Signal | 4~20mA DC |
| Control Output | Relay contacts max 250V AC 10A (inductive load) |
| Delay Time Adjustment | 0.5~8 seconds |
| Dead Band Adjustment | 0.1~4.5% |
| Environmental Temperature | -10C to +60C |
Set the actuator to approximately 50% position using the handwheel and press the AUTO SETTING button once for more than 2 seconds.
A flashing yellow LED indicates an input signal error.
A comprehensive inspection should be performed approximately once a year.