QM AN-01 Emergency Start/Stop Box User Manual

The QM-AN-01 emergency start/stop box provides emergency start/stop control signals to the gas fire control system, and has running indication and fire alarm indication functions.


QM AN-01 Emergency Start/Stop Box User Manual - cover page
Brand
QM-AN-01
Category
Other
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
260 KB
Published
15 March, 2012
Updated
30 September, 2023
MD5 checksum
8FDA9E74B1C8A20933EF7023D00B0DEA

About this manual

The QM AN-01 Emergency Start/Stop Box supplies emergency start and stop signals to a gas fire‑extinguishing controller. It is mounted outside the protected area exit and uses a keyed rotary switch for manual activation.

The manual lists technical parameters, wiring diagrams, terminal assignments, installation dimensions, and safety precautions. It also describes the required power cable size and advises that installation and commissioning be performed by qualified personnel. This manual is written in Chinese.

What's inside

  • Overview
  • Technical Parameters
  • Installation and Wiring
  • Operating Instructions
  • Installation and Safety Precautions

Specifications

Operating Temperature-10 °C to +55 °C
Maximum Humidity≤95 % (40 °C ±2 °C, no condensation)
Working VoltageDC 24 V
Working Current<100 mA
Contact Rating<2 A / 24 V
Power Cable Minimum Size≥1.5 mm² BV cable

Frequently asked questions

What is the working voltage of the QM AN-01 box?

It operates on a 24 V DC supply.

How can the gas release be stopped if no fire is detected?

Rotate the stop key to the stop position, which opens contacts 3 and 4 and interrupts the release signal.

What type of cable should be used for the power line?

Use a BV cable of at least 1.5 mm² cross‑section for the power line.

What are the temperature limits for operating the device?

The device can operate from –10 °C up to +55 °C.

Download PDF (260 KB)