DETRON DIM Series Power Supply User Manual

DIM series product manual, introduces the features and characteristics of DIM series products and usage methods, including precautions before use, safety marks, terminal connection instructions, etc.


DETRON DIM Series Power Supply User Manual - cover page
Brand
DETRON
Category
AC-DC Power
Document type
User Manual
Language
Chinese
Pages
14
File format
PDF
File size
295 KB
Published
13 March, 2012
Updated
30 September, 2023
MD5 checksum
2576E3EB2007F5CE41F09E904C9F1DE1

About this manual

This manual covers the safe operation of DETRON DIM series power supplies. It begins with safety warnings, explains the meaning of each connector, and provides step‑by‑step wiring methods for both single‑unit and parallel/series configurations.

Later sections describe the functional protections (over‑voltage, over‑current, over‑temperature), insulation and dielectric test requirements, installation recommendations, cable and fuse specifications, fan maintenance, and troubleshooting procedures to verify proper operation before service. This manual is written in Chinese.

What's inside

  • Safety Warnings
  • Connector Description
  • Wiring Method
  • Function and Protection
  • Insulation / Dielectric Test
  • Installation Guidelines
  • Cable Recommendations
  • External Fuse Specification
  • Fan Maintenance
  • Troubleshooting

Specifications

Input voltage range85~265VAC (47~63Hz)
Output voltage adjustment range±10% of nominal output voltage
Over‑current protection threshold105% of average rated output current
Insulation resistance>100 MΩ at 500 VDC
Dielectric test voltage (input‑output)3.0 kVAC
External fuse rating (DIM1011 / DIM1511)4 A
External fuse rating (DIM2011 / DIM3011)5 A

Frequently asked questions

What is the input voltage range for the DIM series power supplies?

The input voltage must be between 85 V and 265 V AC at 47 – 63 Hz.

How is over‑current protection triggered?

Over‑current protection activates when the output current exceeds 105 % of the average rated output current.

What safety precautions should be observed before using the power supply?

Do not disassemble or modify the unit, avoid touching internal components that may be high‑voltage or hot, and keep hands and face away while the supply is operating.

How should the remote compensation (+S, –S) lines be connected?

Connect the +S terminal to the load side with a sampling wire; the compensation reduces line voltage drop and must not exceed 0.3 V.

Download PDF (295 KB)

More DETRON Manuals


View all DETRON manuals →