Messko MT-ST160 Series Pointer Thermometer Operating Manual

This document is an operating instruction for Messko brand's pointer thermometer, which introduces the safety instructions, product specifications, installation, electrical connection, indication control and readjustment, adjustment of the gradient, maintenance, and technical data of the compact series thermometers including MT-ST160SK/TT, MT-ST160W, MT-ST160W/TT, MT-ST160WR, and MT-ST160WR/TT.


Messko MT-ST160 Series Pointer Thermometer Operating Manual - cover page
Brand
MR
Document type
User Manual
Language
Chinese
Pages
16
File format
PDF
File size
1.7 MB
Published
11 January, 2012
Updated
28 September, 2023
MD5 checksum
3A883FEBF3407FE3F015966000656439

About this manual

The Messko MT‑ST160 series pointer thermometers are designed for measuring the temperature of power transformers, reactors, and similar equipment. The manual provides safety instructions, product specifications, installation steps, electrical connection details, and adjustment procedures.

The document covers mounting the device on a transformer, routing the capillary tube, connecting microswitches and sensor circuitry, performing gradient adjustments, and routine maintenance. Technical data such as measuring range, tolerance, protection rating, and microswitch specifications are listed in the technical data section. This manual is written in Chinese.

What's inside

  • Safety Instructions
  • Product Specification
  • Installation
  • Electrical Connection
  • Indication Control and Readjustment
  • Gradient Adjustment
  • Maintenance
  • Technical Data
  • Appendix

Specifications

Measuring range-20 °C … 140 °C
Temperature tolerance±3 °C (class 1)
Degree of protectionIP55
Ambient temperature range-50 °C … 80 °C
Microswitch rated current (AC)5 A at 250 VAC (110 VAC)
Microswitch rated current (DC)0.4 A at 250 VDC, 0.6 A at 110 VDC
Adjustable microswitches1 to 6
Sensor output signal4…20 mA, two‑wire
Sensor supply voltage12 V … 30 V DC

Frequently asked questions

What is the specified application of the pointer thermometer?

The pointer thermometer is used to measure the temperature of power transformers, reactors, or similar equipment.

What safety precautions must be observed during installation and operation?

Only qualified personnel may install, commission, operate, or maintain the device; all work on live parts must be performed with power removed or protected, and a ground connection is required.

How many adjustable microswitches can the thermometer have?

The device can be equipped with one to six adjustable microswitches.