This document introduces the installation, maintenance and maintenance of Marley NC fiberglass cooling tower.
About this manual
This manual covers the complete installation process for the Marley NC fiberglass cooling tower, including transportation, receiving, site location, assembly, motor wiring, and mechanical equipment setup. It also details startup procedures, water‑treatment requirements, and seasonal shutdown instructions.
Additional sections provide a maintenance schedule, troubleshooting guidance, and fault‑diagnosis steps, along with safety warnings and contact information for Marley service agents. This manual is written in Chinese.
What's inside
- Cooling Tower Transportation
- Receiving Cooling Tower
- Cooling Tower Location
- Cooling Tower Assembly
- Motor Wiring
- Mechanical Equipment
- Cooling Tower Startup
- Cooling Tower Maintenance
- Water Treatment and Drainage
- Cooling Tower Maintenance Schedule
Specifications
| Water depth for NC8401‑NC8405 models | ≈ 178 mm |
|---|
| Water depth for NC8407‑NC8414 models | ≈ 203 mm |
|---|
| pH range for chlorine treatment | 7.0‑7.6 |
|---|
| Maximum allowable water temperature | 46 °C |
|---|
| Motor overload protection setting | 110 % of name‑plate amperage |
Frequently asked questions
How should the motor overload protection be set?
Set the motor overload protection to 110 % of the name‑plate amperage.
What water depth should be set for NC8401‑NC8405 cooling towers?
Fill the water to about 178 mm depth in the collection tray.
What pH range is required when using sodium hypochlorite for water treatment?
Maintain the water pH between 7.0 and 7.6.
What is the maximum permissible water temperature for safe operation?
The water temperature must not exceed 46 °C.