Yaskawa Varispeed E7 CIMR-E7B Error OL7: High Slip Differential Brake Overload

Yaskawa Varispeed E7 CIMR-E7B inverter · taken from the manufacturer’s manual, pages cited

Error codeOL7

High Slip Differential Brake Overload means the deceleration time does not cause a change in output frequency. The manual's first action is: “• Check whether the load has rotational inertia. • Set the deceleration time (that does not cause OV) to less than the N3-04 setting.”

Model
Yaskawa Varispeed E7 CIMR-E7B
Display shows
High Slip Differential Brake Overload (OL7)
Type
Error code
Source
Manual p. 217

What OL7 means

High Slip Differential Brake Overload p. 257

Common causes

  • The time set by N3-04 does not cause a change in output frequency. p. 257

What to do

  1. • Check whether the load has rotational inertia. • Set the deceleration time (that does not cause OV) to less than the N3-04 setting. p. 257

Before you service the product, read the safety instructions in the manual p. 4.

If OL7 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.

This page summarises what the manufacturer’s manual says about OL7; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.