PHF indicates input phase loss from drive incorrectly supplied, a fuse blown, failure of one phase, 3-phase ATV71W used on a single phase line supply, or unbalanced load. The manual's first action is: “Check the power connection and the fuses Reset Use a 3-phase line Disable the fault by setting [Input phase loss] (IPL) = [No] (nO) (consult the CD-ROM supplied with the drive).”
- Model
- Schneider Electric Altivar 71W
- Display shows
- [INPUT PHASE LOSS] (PHF)
- Type
- Fault code
- Source
- Manual p. 74
What PHF means
[INPUT PHASE LOSS] p. 74
Common causes
- Drive incorrectly supplied or a fuse blown Failure of one phase 3-phase ATV71W used on a single phase line supply Unbalanced load This protection only operates with the drive on load p. 74
What to do
- Check the power connection and the fuses Reset Use a 3-phase line Disable the fault by setting [Input phase loss] (IPL) = [No] (nO) (consult the CD-ROM supplied with the drive). p. 74
Before you service the product, read the safety instructions in the manual p. 41.
If PHF is still not resolved
- contact Schneider Electric service p. 42 “Failure to follow these instructions will result in death, serious physical injury or equipment damage.”
This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.