DPF2 indicates three motor phase loss caused by motor not connected or motor power too low, output contactor open, or instantaneous instability in the motor current. The manual's first action is: “• Check the connections from the drive to the motor • If an output contactor is being used, consult the CD-ROM supplied with the drive • Test on a low-power motor or without a motor: In factory settings mode, motor phase loss detection is active [Output Phase Loss] (OPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high-power drives), deactivate motor phase loss detection [Output Phase Loss] (OPL) = [No] (nO) (consult the CD-ROM supplied with the drive). • Check and optimize the [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) parameters and perform an [Auto tuning] (tUn) operation.”
- Model
- Schneider Electric Altivar 71W
- Display shows
- [3 MOTOR PHASE LOSS] (DPF2)
- Type
- Fault code
- Source
- Manual p. 73
What DPF2 means
[3 MOTOR PHASE LOSS] p. 73
Common causes
- • Motor not connected or motor power too low • Output contactor open • Instantaneous instability in the motor current p. 73
What to do
- • Check the connections from the drive to the motor • If an output contactor is being used, consult the CD-ROM supplied with the drive • Test on a low-power motor or without a motor: In factory settings mode, motor phase loss detection is active [Output Phase Loss] (OPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high-power drives), deactivate motor phase loss detection [Output Phase Loss] (OPL) = [No] (nO) (consult the CD-ROM supplied with the drive). • Check and optimize the [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) parameters and perform an [Auto tuning] (tUn) operation. p. 73
Before you service the product, read the safety instructions in the manual p. 41.
If DPF2 is still not resolved
- contact Schneider Electric service p. 42 “Failure to follow these instructions will result in death, serious physical injury or equipment damage.”
This page summarises what the manufacturer’s manual says about DPF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.
