Fault codebUF-

The code [BU PROTECTION] indicates a short-circuit output from the braking unit or that the braking unit is not connected. The manual's first action is: “See page 206”

Model
Schneider Altivar 61
Display shows
[BU PROTECTION] (bUF-)
Type
Fault code
Source
Manual p. 187

What bUF- means

[BU PROTECTION] p. 187

Common causes

  • Short-circuit output from braking unit p. 187
  • Braking unit not connected p. 187

What to do

  1. See page 206 p. 187
  2. Check the wiring of the braking unit and the resistor Check the braking resistor p. 187
  3. Check the monitoring of this fault must be disabled by the [Brake res. fault Mgt] (bUb) parameter, page 208 if there is no braking unit or resistor connected to the drive, at and above 55 kW (75 HP) for ATV61 HecoM3X and at and above 90 kW (120 HP) for ATV61 HecoN4. p. 187

Before you service the product, read the safety instructions in the manual p. 10.

If bUF- is still not resolved

  • Disconnect all power including external control power p. 4
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about bUF-; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.