Riello Sentinel Dual Error A63

Riello Sentinel Dual UPS · taken from the manufacturer’s manual, pages cited

Fault codeA63

The batteries are flat and the UPS is waiting for voltage to recover above threshold. The manual's first action is: “Wait until the batteries have recharged or force power-on manually by holding down the "ON" button for at least 2 seconds.”

Model
Riello Sentinel Dual
Display shows
A63
Type
Fault code
Source
Manual p. 27

What A63 means

THE BATTERIES ARE FLAT; THE UPS IS WAITING FOR THE BATTERY VOLTAGE TO EXCEED THE SET THRESHOLD p. 27

Common causes

  • THE BATTERIES ARE FLAT; THE UPS IS WAITING FOR THE BATTERY VOLTAGE TO EXCEED THE SET THRESHOLD p. 27
  • Waiting for battery charging p. 27

What to do

  1. Wait until the batteries have recharged or force power-on manually by holding down the "ON" button for at least 2 seconds. p. 27

Before you service the product, read the safety instructions in the manual p. 26.

If A63 is still not resolved

  • contact service / dealer p. 18
    “In order to optimise performance, in ECO mode, the load is normally powered by the bypass.”

This page summarises what the manufacturer’s manual says about A63; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Riello. Found a mistake? Report an error.