Fault code14
Thermal Fuse indicates a problem with gas type mismatch or restricted airflow, possibly due to foreign materials in combustion chamber or exhaust piping. The manual's first action is: “Check for restrictions in air flow around unit and vent terminal.”
- Model
- Rheem 305, 505, 705
- Display shows
- Thermal Fuse (14)
- Type
- Fault code
- Source
- Manual p. 10
What 14 means
Thermal Fuse p. 10
Common causes
- Check gas type of unit and ensure it matches gas type being used. p. 10
- Check for low water flow in a circulating system causing short-cycling. p. 10
- Check for foreign materials in combustion chamber and/or exhaust piping. p. 10
- Check heat exchanger surface for hot spots which indicate blockage due to scale build-up. p. 10
- Measure resistance of safety circuit. p. 10
- Check for improper conversion of product. p. 10
What to do
- Check for restrictions in air flow around unit and vent terminal. p. 10
- Ensure dip switches are set to the proper position. p. 10
- Check heat exchanger surface for cracks and/or separations. p. 10
- Refer to instructions in manual for flushing heat exchanger. p. 10
- Ensure high fire and low fire manifold pressure is correct. p. 10
Before you service the product, read the safety instructions in the manual p. 4.