Omron CS1W-ETN21, CJ1W-ETN21 Error 03C2: FINS/TCP packet discarded

Omron CS1W-ETN21, CJ1W-ETN21 · taken from the manufacturer’s manual, pages cited

Error code03C2

FINS/TCP packet discarded due to network or memory issues. The manual's first action is: “Have the FINS/TCP connection status checked when a SEND(090), REC V(098), or CMND(490) instruction is executed in the ladder program.”

Model
Omron CS1W-ETN21, CJ1W-ETN21
Display shows
FINS/TCP packet discarded (03C2)
Type
Error code
Source
Manual p. 231

What 03C2 means

FINS/TCP packet discarded p. 231

Common causes

  • 01 to 10: Connection number p. 231
  • 02: Reopened because remote node closed p. 231
  • 03: Reopened because of reception error p. 231
  • 04: Reopened because of transmission error p. 231
  • 05: Reopened because RST received from remote node p. 231
  • 06: Reopened because of no keep-alive response p. 231
  • 07: Illegal FINS/TCP procedure p. 231
  • 08: Insufficient memory during server processing p. 231
  • 09: Insufficient memory during client processing p. 231
  • 0A: Insufficient memory during node switching p. 231

What to do

  1. Have the FINS/TCP connection status checked when a SEND(090), REC V(098), or CMND(490) instruction is executed in the ladder program. p. 231
  2. Refer to Operation Manual, Construction of Applications: SECTION 7, and correct the remote node (application on a personal computer). p. 231
  3. There is too much load (traffic) on the Ethernet Unit. Correct the system so that traffic is not concentrated. p. 231

If 03C2 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.

This page summarises what the manufacturer’s manual says about 03C2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.