FOR nesting overflow means the NEXT command with respect to the FOR command does not exist within the user program, or the FOR command does not exist before the NEXT command, or the NEXT command exists before the FOR command. The manual lists no action for this code.
- Model
- Hitachi EH-150
- Display shows
- FOR nesting overflow (H0046)
- Type
- Error code
- Source
- Manual p. 215
What H0046 means
FOR nesting overflow p. 215
Common causes
- The NEXT command with respect to the FOR command does not exist within the user program. p. 215
- The FOR command does not exist before the NEXT command. p. 215
- The NEXT command exists before the FOR command. p. 215
- A FOR command with the same code number n is programmed. p. 215
- a NEXT command with the same code number n is programmed. p. 215
- When WM000=0 since FOR 1(I/WM000) to NEXT 1 is prioritized, jump will not be performed over NEXT from FOR 2 to NEXT 2. At this time, NEXT 2 generates a FOR 2 undefined error. p. 215
- When WM002 =0 For 2 will not do anything. Therefore, NEXT 2 will generate a FOR 2 undefined error. p. 215
- There are more than 6 nesting levels of FOR to NEXT p. 215
If H0046 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Hitachi service.
This page summarises what the manufacturer’s manual says about H0046; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Hitachi. Found a mistake? Report an error.