Torque overload error means the servo drive is locked and cannot rotate freely because the torque is too high, preventing the speed from exceeding the GP8 value for longer than the GP7 value. The manual's first action is: “Release the motor. If the error occurs without obvious cause, increase the values of GP7 (F235) and/or GP8 (F236). If GP7 is set to 0, this error message will never appear.”
- Model
- Fagor Servo Drive System
- Display shows
- Torque overload error (203)
- Type
- Error code
- Source
- Manual p. 386
What 203 means
Torque overload error p. 386
Common causes
- The servo drive is locked and cannot rotate freely. Because the torque is too high, the speed does not exceed the GP8 value during a time interval that is greater than the GP7 (F235) value. p. 386
- The servo drive is locked and cannot rotate freely. Because the torque is too high, the rotational speed cannot exceed the GP8 value during a time interval that is greater than the GP7 value. p. 386
- If GP7 is set to 0, this problem will never occur. p. 386
- Strengthen the power cable connections. p. 386
What to do
- Release the motor. If the error occurs without obvious cause, increase the values of GP7 (F235) and/or GP8 (F236). If GP7 is set to 0, this error message will never appear. p. 386
- Release the motor. If the error appears without a cause, increase the values of GP7 and/or GP8. p. 386
- Check that there are no loose connections or phase swaps. p. 386
Before you service the product, read the safety instructions in the manual p. 444.
If 203 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Fagor service.