ABB ACS550-02 / ACS550-U2 Error 2024: ENCODER ERROR

AC drive · taken from the manufacturer’s manual, pages cited

Alarm code2024

This code indicates encoder error. The manual's first action is: “The drive is not detecting a valid encoder signal. Check for and correct. • Encoder presence and proper connection (reverse wired, loose connection, or short circuit). • Voltage logic levels are outside of the specified range. • A working and properly connected Pulse Encoder Interface Module, OTAC-01. • Wrong value entered in parameter 5001 PULSE NR. A wrong value will only be detected if the error is such that the calculated slip is greater than 4 times the rated slip of the motor. • Encoder is not being used, but parameter 5002 ENCODER ENABLE = 1 (ENABLE).”

Model
ABB ACS550-02 / ACS550-U2
Display shows
ENCODER ERROR (2024)
Type
Alarm code
Source
Manual p. 282

What 2024 means

ENCODER ERROR p. 282

What to do

  1. The drive is not detecting a valid encoder signal. Check for and correct. • Encoder presence and proper connection (reverse wired, loose connection, or short circuit). • Voltage logic levels are outside of the specified range. • A working and properly connected Pulse Encoder Interface Module, OTAC-01. • Wrong value entered in parameter 5001 PULSE NR. A wrong value will only be detected if the error is such that the calculated slip is greater than 4 times the rated slip of the motor. • Encoder is not being used, but parameter 5002 ENCODER ENABLE = 1 (ENABLE). p. 282

Before you service the product, read the safety instructions in the manual p. 5.

If 2024 is still not resolved

  • Contact your local Authorized Service Centre for service. p. 6
    “contact your local Authorized Service Centre for service”

This page summarises what the manufacturer’s manual says about 2024; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.