ABB ACS 502/504 Error 2: OVER TEMP

ABB ACS 502/504 adjustable frequency AC drive · taken from the manufacturer’s manual, pages cited

Fault code2

Code 2 (OVER TEMP) means the heatsink temperature has been above 185°F (85°C) and has not fallen below 167°F (75°C). The manual's first action is: “Check that ambient temperature is < 104°F (< 40°C). Check that the drive was not overloaded for too long. Check the fan and air flow. Check the fuses on SNA 7902 INP. Check that T61 primary and secondary connections are OK. Check heatsink fan, remove any dust or dirt. If the fault persists, contact a service representative. If the temperature display was negative, check the line fuses.”

Model
ABB ACS 502/504
Display shows
OVER TEMP (2)
Type
Fault code
Source
Manual p. 76

What 2 means

OVER TEMP p. 76

Common causes

  • The heatsink temperature has been above 185°F (85°C) and has not fallen below 167°F (75°C). Restricted air flow caused by dust or inappropriate installation; overloading or a component failure (fan, power semiconductors). If the display shows a negative temperature, when the ambient (and heatsink) is obviously warmer, the thermostat S1 has probably opened (due to Rectifier bridge overtemperature). If this fault appears at start, it is possible that terminal X307 on Main Circuit Interface Card is loose. p. 76

What to do

  1. Check that ambient temperature is < 104°F (< 40°C). Check that the drive was not overloaded for too long. Check the fan and air flow. Check the fuses on SNA 7902 INP. Check that T61 primary and secondary connections are OK. Check heatsink fan, remove any dust or dirt. If the fault persists, contact a service representative. If the temperature display was negative, check the line fuses. p. 76

Before you service the product, read the safety instructions in the manual p. 75.

If 2 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.

This page summarises what the manufacturer’s manual says about 2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.