Alarm code4002
INP PHASE B LOSS occurs when phase B input is lost, often due to loose wiring or voltage issues. The manual's first action is: “Check J8 connector Check black wire on input block Check incoming voltage, phase to ground”
- Model
- ABB ACH550
- Display shows
- INP PHASE B LOSS (4002)
- Type
- Alarm code
- Source
- Manual p. 72
What 4002 means
INP PHASE B LOSS p. 72
Common causes
- Alarm will occur in drive mode. In bypass, alarm will occur if bypass contactor has not closed. Unit will trip on Fault 3011 if the bypass contactor is closed p. 72
- Loose J8 connector p. 72
- Loose wiring on Contactor assembly. p. 72
- Blown upstream fuse p. 72
What to do
- Check J8 connector Check black wire on input block Check incoming voltage, phase to ground p. 72
Before you service the product, read the safety instructions in the manual p. 2.
If 4002 is still not resolved
- contact the factory or your local Authorized Service Center for repair or replacement. p. 2 “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”