ABB ACH550 Error 1005: PAR PCU 2

AC drive · taken from the manufacturer’s manual, pages cited

Fault code1005

PAR PCU 2 occurs when power control parameters are inconsistent, likely due to incorrect motor nominal kVA or power settings. The manual's first action is: “Improper motor nominal kVA or motor nominal power. Check for the following: 1.1 ≤ (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / P_N) ≤ 3.0 Where: P_N = 1000 * 9909 MOTOR NOM POWER (if units are kW) or P_N = 746 * 9909 MOTOR NOM POWER (if units are HR, e.g. in US)”

Model
ABB ACH550
Display shows
PAR PCU 2 (1005)
Type
Fault code
Source
Manual p. 28

What 1005 means

PAR PCU 2 p. 28

Common causes

  • Parameter values for power control are inconsistent. p. 28

What to do

  1. Improper motor nominal kVA or motor nominal power. Check for the following: 1.1 ≤ (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / P_N) ≤ 3.0 Where: P_N = 1000 * 9909 MOTOR NOM POWER (if units are kW) or P_N = 746 * 9909 MOTOR NOM POWER (if units are HR, e.g. in US) p. 28

Before you service the product, read the safety instructions in the manual p. 2.

If 1005 is still not resolved

  • contact the factory or your local Authorized Service Center for repair or replacement. p. 2
    “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”