SERIAL 1 ERR means the master system is down, the communication connection is bad, or the time-out selection for the drive is too short for the given installation. The manual's first action is: “resolve problem with master system.”
- Model
- ABB ACH550-01/02/U1/U2
- Display shows
- SERIAL 1 ERR (28)
- Type
- Error code
- Source
- Manual p. 19
What 28 means
SERIAL 1 ERR p. 19
Common causes
- The master system is down. p. 19
- The communication connection is bad. p. 19
- The time-out selection for the drive is too short for the given installation. The master is not polling the drive within the specified time-out delay. p. 19
What to do
- resolve problem with master system. p. 19
- check communication connection at the drive. p. 19
- increase the time set by parameter 3019 COMM FAULT TIME. p. 19
Before you service the product, read the safety instructions in the manual p. 30.
If 28 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.