The Gemotech RemoDAQ-8055 is an intelligent sensor-to-computer interface module featuring 8 isolated digital inputs and 8 isolated digital outputs. It utilizes a built-in microprocessor to handle signal conditioning, isolation, and data conversion via the RS-485 protocol. The device is designed for critical applications, offering 3000Vdc optical isolation and compatibility with various input voltage levels.

Read online

Gemotech RemoDAQ-8055 specifications

Channels8 channel isolated DI and 8 channel isolated DO
Isolation3000Vdc optical isolation
Output Voltage5~40V open collector
Power Supply10~30VDC
Power Consumption1.2W
Operating Temperature-20 ~ 70° C

Source: Gemotech RemoDAQ-8055 User's Manual

All Gemotech RemoDAQ-8055 documents by type

User Manual 2

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What is the default baudrate for the RemoDAQ-8055?

The default baudrate is 9600 bps.

From: Gemotech RemoDAQ-8055 User's Manual

Can the module handle both dry and wet contacts simultaneously?

Yes, in the default setting mode, the jumpers support dry and wet contact at the same time.

From: Gemotech RemoDAQ-8055 User's Manual

What are the default address and baud rate of the module?

The default address is 01 and the default baud rate is 9600 bps.

From: Beijing Jizhi Da RemoDAQ-8055 Module User Manual

How can I activate the INIT mode to restore factory settings?

Power off the module, short the INIT* terminal to GND, power on, then send the command $002 at 9600 bps.