Key facts
- Brand
- Festo
- Model
- VABA-S6-1-AP
- Category
- Automation control Equipment
- Industry
- Industrial
- Documents
- 2
- Languages
- ZH
- Last added
- 2026-10-29
Start here

Festo VABA-S6-1-AP Electrical Interface Operation Manual
The Festo VABA-S6-1-AP is an electrical interface designed to connect VTSA-MP(-NPT) or VTSA-F-MP(-NPT) valve islands with the CPX-AP-I automation system. The document serves as a user guide for installation, assembly, and operation of this component. This manual is written in Chinese.
Read onlineFesto VABA-S6-1-AP specifications
| Operating Temperature | -5 ... +50 °C |
|---|---|
| Storage Temperature | -20 ... +60 °C |
| Protection Class | IP65 |
| Max Valve Coils | 24 |
| Address Space (Input/Output) | - / 3 bytes |
| Module Code | 0x2022 / 8226d |
| Logic Power Voltage | 24 V DC ± 25 % |
| Load Power Voltage | 24 V DC ± 10 % |
Source: Festo VABA-S6-1-AP Electrical Interface Operation Manual
All Festo VABA-S6-1-AP documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the maximum number of valve coils controlled by this interface?
The VABA-S6-1-AP can control a maximum of 24 electromagnetic valves.
From: Festo VABA-S6-1-AP Electrical Interface Operation Manual
What are the voltage limits for the logic power supply?
The logic power supply (PS) operates at 24 V DC with a tolerance of ±25%.
From: Festo VABA-S6-1-AP Electrical Interface Operation Manual
What does the VABA-S6-1-AP connect?
It connects VTSA-MP(-NPT) or VTSA-F-MP(-NPT) valve manifolds to the CPX-AP-I automation system.
From: Festo VABA-S6-1-AP Electric Interface Operation Manual
What type of power supply must be used?
Use a protective extra-low voltage (PELV) circuit according to IEC60204-1/EN60204-1.
From: Festo VABA-S6-1-AP Electric Interface Operation Manual