The ZX3030F is a verification device for the four‑remote functions (telemetry, tele‑signal, tele‑control, tele‑adjustment) of substation automation systems. It uses DSP, GPS timing and wireless communication technologies to test and calibrate RTU devices, providing AC and DC power outputs, data management and parameter settings.

The manual is organized into sections covering an overview, main features, technical specifications, front and rear panel descriptions, keyboard functions, power‑on procedures, standalone operation, networked operation, safety notes and appendices with additional calibration notes and a FAQ table. This manual is written in Chinese.

What's inside

  • Overview
  • Main Features and Characteristics
  • Technical Specifications
  • Front Panel
  • Rear Panel
  • Keyboard
  • Power‑On Procedure
  • Standalone Operation
  • Networked Operation
  • Usage Precautions

Specifications

AC Voltage Output Range25 V–600 V
AC Current Output Range1 A–25 A
Output Accuracy±0.05 %
Frequency Adjustment Range45 Hz–65 Hz
Power Accuracy±0.05 % (reactive ≤0.2 %)
Voltage/Current Waveform Distortion≤0.2 %
Total Harmonic Distortion≤0.2 %
Operating Temperature Range-20 °C to 40 °C
Relative Humidity Range10 %–90 %

Frequently asked questions

How do I start the device if it does not output after power‑on?

Press the “启动” (Start) button; if the internal power protection has engaged, releasing the fault and pressing this button will restart the internal power supply.

What must be done before outputting DC current?

Ensure the AC current output terminals are open‑circuit; otherwise the DC current output will be abnormal.