This quick installation guide covers mounting, grounding, sensor connections, interface wiring (AI, DI, DO, RS485/232, Network), antenna setup, SIM card…
This manual provides a quick installation guide for the Yunlun IOTH-4004A IoT Monitoring Host. It details the physical installation process, including fixing the chassis to a rack and connecting the ground wire. The guide also explains how to connect external sensors to the analog input (AI) and digital input (DI) interfaces. This manual is written in Chinese.
| Analog Input Range | Current: 4~20mA / Voltage: 0~5V |
|---|---|
| Analog Input Channels | 8 channels (AI1~AI8) |
| Digital Input Channels | 16 channels (DI1~DI16) |
| Relay Output Channels | 8 channels (DO1~DO8) |
| Relay Contact Rating | 1A@120VAC, 1A@24VDC |
| Serial Interfaces | 4 interfaces (COM1~COM4) |
| Power Supply | 220V AC (customizable to 12V/-48V DC) |
Use jumper J1 to J8; short pins 2 and 3 for current input, or leave pins 1, 2, and 3 floating for voltage input.
The default is closed alarm (normal state is open, alarm state is closed).
Short pins 1 and 2 of the corresponding jumper (JP1 to JP8) to set the port to Normally Closed.
The device supports standard 25mm*15mm SIM cards (Large cards) from China Unicom or China Mobile.