The Yongxu Weiye TZID-C Smart Locator Installation and Operation Manual provides step‑by‑step instructions for mounting, wiring, parameter setup, and…
This guide covers the mechanical and electrical installation of the TZID‑C smart locator, including air‑line connections, standard interface wiring, and power requirements. It also explains the required pressure limits and signal specifications for safe operation.
The manual details parameter configuration, automatic adjustment procedures, and the various operating modes (self‑adaptive, fixed, manual, and sensor‑based). It includes information on alarm settings, EEPROM storage of parameters, and troubleshooting of fault codes. This manual is written in Chinese.
| Maximum supply pressure | 7 BAR |
|---|---|
| Input signal range | 4‑20 mA |
| Load resistance (max) | 410 Ω |
| Position feedback output | 4‑20 mA, DCS+24 V supply |
| Straight travel angle range | -28° to +28° |
| Angular travel angle range | -57° to +57° |
The maximum supply pressure is 7 BAR.
Hold the MODE key, press the ⇧ key until “P1.1” appears, release MODE, then hold ENTER for 3 seconds until the countdown reaches zero and release ENTER.
Hold the MODE key and press the ⇧ key until “1.0 CTRL_ADP” is displayed, then release the MODE key.
The default input signal limits are 4 mA minimum and 20 mA maximum.