User manual for the YTC3223 Transformer Winding Deformation Tester, covering instrument overview, technical specifications, connection methods, and software…
The YTC3223 Transformer Winding Deformation Tester is a non-destructive testing device designed to detect internal structural faults in power transformers ranging from 63kV to 500kV. It utilizes Frequency Response Analysis (FRA) to measure changes in coil parameters, such as twisting, bulging, shifting, or short circuits, by analyzing frequency response characteristics. This manual is written in Chinese.
| Frequency Range (Segmented Sweep) | 0.5kHz - 1MHz |
|---|---|
| Amplitude Measurement Range | -100dB to +20dB |
| Amplitude Measurement Accuracy | 0.1dB |
| Signal Input Impedance | 1MΩ |
| Signal Output Impedance | 50Ω |
| Measurement Repeatability | 99.5% |
| Instrument Dimensions | 345x250x120 mm |
| Total Weight | 10Kg |
It is suitable for detecting internal structural faults in power transformers from 63kV to 500kV.
No, testing can be completed without removing the transformer cover or dismantling components, only by removing the busbar connections.
It fully meets the technical conditions of the power industry standard DL/T911-2004.