XSEEC BL Series Frame Capacity Residual Current Circuit Breaker User Manual

XSEEC BL series frame capacity residual current circuit breaker user manual with model dimensions, usage precautions, terminal torque values, and insulation…


XSEEC BL Series Frame Capacity Residual Current Circuit Breaker User Manual - cover page
Brand
XSEEC
Category
switch
Document type
User Manual
Language
Chinese
Pages
1
File format
PDF
File size
309 KB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
5CA95DDC0F33A46BF29F785AF87B43B2

About this manual

This manual covers XSEEC BL series frame capacity residual current circuit breakers. It lists model variants with outline and installation dimensions and gives usage precautions for installation, operation, and maintenance.

It also specifies standard terminal screw tightening torques, wiring-related precautions, and instructions for using insulation barriers to improve insulation between breaker terminals. This manual is written in Chinese.

What's inside

  • Usage precautions
  • Standard terminal screw tightening torque
  • Insulation barrier usage instructions
  • Outline and installation dimensions
  • Terminal wiring methods

Specifications

BL50-SN outline dimensionsa 75 mm, b 100 mm, c 130 mm, ca 68 mm, bb 86 mm, aa 111 mm
BL100-SN outline dimensionsa 90 mm, b 120 mm, c 155 mm, ca 68 mm, bb 90 mm, aa 134 mm
BL160-SN outline dimensionsa 105 mm, b 140 mm, c 165 mm, ca 68 mm, bb 92 mm, aa 126 mm
BL400-SN outline dimensionsa 140 mm, b 185 mm, c 257 mm, ca 103 mm, bb 155 mm, aa 194 mm
BL630-HN outline dimensionsa 210 mm, b 280 mm, c 275 mm, ca 103 mm, bb 155 mm, aa 243 mm
Hexagon M12 terminal screw tightening torque40.8-51.0 N·m

Frequently asked questions

Can a three-pole BL series breaker be used in a three-phase four-wire system?

No. Three-pole residual current circuit breakers must not be used in three-phase four-wire systems.

How should a three-pole breaker be connected in a single-phase system?

Connect the power to poles A and C.

Can BL series breakers be fed from the bottom?

No, BL series residual current circuit breakers cannot be bottom-fed.

What must be done after an automatic trip?

Eliminate the fault cause before turning the handle to ON.