Wilo SC Circulation Pump User Manual

User manual for Wilo SC circulation pumps, covering installation, operation modes, wiring, and technical specifications.


Wilo SC Circulation Pump User Manual - cover page
Brand
Wilo
Document type
User Manual
Language
Chinese
Pages
12
File format
PDF
File size
984 KB
Published
07 November, 2026
Updated
07 November, 2026
MD5 checksum
10769C442F8C55F50D6E92286D9B4948

About this manual

This manual provides instructions for installing and operating Wilo SC circulation pumps in hot water heating systems. It details pump components, wiring procedures, and three operating modes: constant speed, Δp-v, and Δp-c. Technical specifications, performance curves, and fault troubleshooting are also included.

The pump must be installed in pressurized water systems only. Wiring must be performed by a qualified technician. Operating modes can be adjusted using the control button, with factory settings preset for constant speed and curve III. This manual is written in Chinese.

What's inside

  • General Information
  • Pump Description
  • Pump Wiring
  • Pump Control
  • Pump Operating Modes
  • Technical Data
  • Faults, Reasons and Removal

Specifications

Power Supply1 ~ 230 V, 50 - 60 Hz
Power Input (Min./Max.)3 / 43 W for Wilo PARA 25/6 SC, 2 / 75 W for Wilo PARA 25/8 SC
Max. Speed4300 rpm for Wilo PARA 25/6 SC, 4800 rpm for Wilo PARA 25/8 SC
IP RatingIPX4D
Fluid Working Temperature0 - 100 °C at 58 °C ambient temperature
Max. Static Pressure10 bar
Max. Head6.7 m for Wilo PARA 25/6 SC, 8.4 m for Wilo PARA 25/8 SC

Frequently asked questions

What are the operating modes for the Wilo SC pump?

The pump has three operating modes: constant speed, Δp-v (variable differential pressure), and Δp-c (constant differential pressure).

How do I reset the pump to factory settings?

Hold the operating button for at least 4 seconds while the pump is off, then reconnect power.

What is the maximum power input for the Wilo PARA 25/8 SC?

The maximum power input is 75 W.

What is the minimum pressure required at the pump suction port to avoid cavitation?

Minimum pressure is 0.5 mH2O at 50 °C for Wilo PARA 25/6 SC and 4.5 mH2O at 95 °C for Wilo PARA 25/8 SC.