Detailed specifications, standard equipment, and performance data for the Waukesha VHP3604GSI/GSID gas Enginator generating system.
The VHP® Series Four® Gas Enginator® Generating System (model VHP3604GSI/GSID) delivers 500‑600 kW of continuous power and incorporates Waukesha’s Engine System Manager (ESM®) for integrated control of spark timing, speed, air‑fuel ratio, and diagnostics. The system includes a turbocharged, intercooled gas‑fueled engine with six interchangeable cylinder heads and a brushless exciter generator.
Standard equipment covers a dry‑type air cleaner, manual barring device, heavy‑duty bearings, a control system with MODBUS RTU communication, multiple cooling options (radiator, heat exchanger, or remote radiator), and a full suite of monitoring sensors for oil pressure, temperature, and exhaust O₂. Performance tables provide fuel consumption, heat rejection, and airflow data for both 50 Hz and 60 Hz configurations.
| Continuous Power Rating | 500‑600 kW |
|---|---|
| Bore × Stroke | 9.375" (238 mm) × 8.5" (216 mm) |
| Voltage / Frequency | 480/277 V 60 Hz and 400/230 V 50 Hz |
| Fuel Pressure (GSI) | 30 PSIG min – 50 PSIG max |
| Compression Ratio | 8:1 |
The Enginator is rated for 500 kW to 600 kW of continuous power.
Customers can choose a mounted radiator with pusher fan, a heat exchanger with expansion tanks, or a remote radiator cooling system.
The control system complies with Canadian Standards Association Class I, Division 2, Group D hazardous‑location requirements.
The GSI fuel system operates with a pressure range of 30 PSIG minimum to 50 PSIG maximum.