This manual describes the Modbus RTU integration for Volcano EC and WING EC units, detailing BMS cable connections, memory registers, and operational…
This document serves as a device integration manual for the Volcano EC and WING EC units, focusing on Modbus RTU communication. It provides instructions for connecting Building Management System (BMS) cables and explains the data blocks used by the devices. Key information includes wiring diagrams for RS 485 connections and analog outputs, as well as details on how to configure the units via memory registers. This manual is written in Polish.
| Communication Protocol | Modbus RTU |
|---|---|
| Data Readout Interval | not more often than every 1000ms |
| Timeout | 1000ms |
| Minimum Timeout | 500ms |
Data readout is recommended not more often than every 1000ms to avoid errors.
Shortening the timeout below 500ms is possible but requires tests depending on the object conditions.
Data should not be saved cyclically (e.g., every second) but only when the parameter value changes.
Attempting to record two or three registers at the same time leads to an error message.