V-EA Series UL508 manual motor controller datasheet covering ratings, trip curves, short-circuit withstand, terminals, temperatures, and catalog numbers.
The V-EA-Series is a two-pole UL508 manual motor controller with C-Trip thermal overload characteristics. The datasheet lists weight by current range, dimensions, thermal-overload trip curves for 0.3 A through 63 A, and UL/CSA short-circuit withstand ratings.
It also covers calibration, operating and storage temperatures, terminal size and torque, IP20 terminal protection, UL508 listing E137938, and rated current/catalog number table entries from 0.3 A/2C03UM through 63 A/2C63UM.
| Number of poles | 2 |
|---|---|
| Trip type | C-Trip |
| Standard pack | 6 |
| Weight, 0.3 A to 32 A | 1.8 kg (3.97 lb.) |
| Weight, 40 A to 63 A | 1.98 kg (4.37 lb.) |
| Voltage rating | 480Y/277 VAC |
| Short-circuit withstand rating, UL/CSA | 0.3-60 A: 10 kA with UL-listed RK5 back-up fuse or MCCB; 0.3-10 A: 10 kA; 13-60 A: 5 kA |
| Interrupting capacity, VDE | 0.3-63 A: 10 kA |
| Calibration temperature | 40°C (104°F) |
| Operating temperature | -25°C to 55°C (-13°F to 131°F) |
| Storage temperature | -40°C to 70°C (-40°F to 158°F) |
| Terminal size acceptability | Top: 18-3 AWG; Bottom: 18-2 AWG (line/load reversible) |
| Terminal torque | 20 lb.in. |
| Terminal protection degree | IP20 |
| Approvals | UL508 Listed E137938 |
The listed voltage rating is 480Y/277 VAC.
The operating temperature range is -25°C to 55°C (-13°F to 131°F).
The terminal protection degree is IP20.
For 13-60 A models, the UL/CSA short-circuit withstand rating is 5 kA.