V-EA Series UL508 Manual Motor Controller Datasheet

V-EA Series UL508 manual motor controller datasheet covering ratings, trip curves, short-circuit withstand, terminals, temperatures, and catalog numbers.


V-EA Series UL508 Manual Motor Controller Datasheet - cover page
Brand
Vea
Category
motor starter
Document type
Datasheet
Language
English
Pages
1
File format
PDF
File size
533 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
11C5556E2DBE9DAEC1DCDA7D1ED4F122

About this manual

The V-EA-Series is a two-pole UL508 manual motor controller with C-Trip thermal overload characteristics. The datasheet lists weight by current range, dimensions, thermal-overload trip curves for 0.3 A through 63 A, and UL/CSA short-circuit withstand ratings.

It also covers calibration, operating and storage temperatures, terminal size and torque, IP20 terminal protection, UL508 listing E137938, and rated current/catalog number table entries from 0.3 A/2C03UM through 63 A/2C63UM.

What's inside

  • Thermal overload tripping curves
  • Short circuit withstand ratings
  • Calibration temperature
  • Operating temperature
  • Storage temperature
  • Terminal size acceptability
  • Terminal torque
  • Terminal protection degree
  • Standard dual connection terminal
  • Rated current and catalog numbers

Specifications

Number of poles2
Trip typeC-Trip
Standard pack6
Weight, 0.3 A to 32 A1.8 kg (3.97 lb.)
Weight, 40 A to 63 A1.98 kg (4.37 lb.)
Voltage rating480Y/277 VAC
Short-circuit withstand rating, UL/CSA0.3-60 A: 10 kA with UL-listed RK5 back-up fuse or MCCB; 0.3-10 A: 10 kA; 13-60 A: 5 kA
Interrupting capacity, VDE0.3-63 A: 10 kA
Calibration temperature40°C (104°F)
Operating temperature-25°C to 55°C (-13°F to 131°F)
Storage temperature-40°C to 70°C (-40°F to 158°F)
Terminal size acceptabilityTop: 18-3 AWG; Bottom: 18-2 AWG (line/load reversible)
Terminal torque20 lb.in.
Terminal protection degreeIP20
ApprovalsUL508 Listed E137938

Frequently asked questions

What is the voltage rating of the V-EA manual motor controller?

The listed voltage rating is 480Y/277 VAC.

What is the operating temperature range?

The operating temperature range is -25°C to 55°C (-13°F to 131°F).

What is the terminal protection degree?

The terminal protection degree is IP20.

What is the UL/CSA short-circuit withstand rating for 13-60 A models?

For 13-60 A models, the UL/CSA short-circuit withstand rating is 5 kA.

Download PDF (533 KB)

More Vea Manuals


View all Vea manuals →