Installation sheet for the Signature Series KI-OSD Intelligent Optical Smoke Detector: installation, testing, maintenance and specifications.
This installation sheet covers the Signature Series model KI-OSD Intelligent Optical Smoke Detector, an intelligent device that uses an advanced optical sensing chamber to detect smoke. The detector analyzes data from the sensing chamber to recognize smoke from a fire while ignoring nuisance non-fire sources, and reports to the Fire Alarm Control Panel through a compatible base. An LED indicator shows normal (green flashing) and alarm/active (red flashing) states, and a self-locking tab secures the unit.
The sheet gives installation notes, the steps for attaching the detector to its base, initial installation and sensor function tests, and maintenance guidance with references to NFPA and CAN/ULC standards. A specifications section lists operating voltage, current, vibration, air velocity, mounting distance, compatible bases and detector testers, operating and storage environment, and regulatory information including UL/ULC smoke sensitivity range and FCC/Industry Canada compliance.
| Operating voltage | 15.20 to 19.95 VDC |
|---|---|
| Current (normal / alarm) | 32 uA / 45 uA |
| Vibration level | 10 to 35 Hz, amplitude 0.01 in. |
| Air velocity | 0 to 4,000 ft./min (0 to 20.32 m/s) |
| Wall mounting distance from ceiling | 12 in. (305 mm) max. |
| Operating temperature | 32 to 120°F (0 to 49°C) |
| Relative humidity | 0 to 93% noncondensing |
| Storage temperature | −4 to 140°F (−20 to 60°C) |
| Environmental compensation | Automatic |
| Compatible detector testers | Testifire 1000, Testifire 2000 |
| North American standards | CAN/ULC-S529, UL 268-7, UL 268A |
| UL/ULC smoke sensitivity range | 0.5 to 4.36 %/ft. (1.63 to 13.62 %/m) obscuration |
A green LED indicator flashes in the normal state with no action required, and a red LED indicator flashes in the alarm/active state, indicating that the area should be evacuated.
The detector is attached to the base by rotating it clockwise until it snaps into the locked position, after the base has been installed and wired.
The smoke sensor can be activated using No Climb Products model Smoke Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol spray, a smoke generator, or the Testifire detector tester.
The detector operates on 15.20 to 19.95 VDC.