TIME MARK Model 295-120/295-240 Capacitor Trip Device Data Sheet

TIME MARK Model 295-120/295-240 Capacitor Trip Device data sheet covering specifications, installation, troubleshooting, and warranty.


TIME MARK Model 295-120/295-240 Capacitor Trip Device Data Sheet - cover page
Brand
TIME MARK
Category
Industrial Supply
Document type
Datasheet
Language
English
Pages
2
File format
PDF
File size
376 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
E15E2F8D5AAE5CA1201B924486D35A1C

About this manual

The TIME MARK Model 295-120/295-240 Capacitor Trip Device is used to trip circuit breakers using energy stored in a capacitor. The capacitor is kept charged during normal operation by a half-wave silicon rectifier and holds sufficient charge to trip the breaker for at least 12 seconds after charging voltage is removed.

The device is available in 120 VAC and 240 VAC versions. It requires no calibration or adjustments, and a low-energy lamp gives a visual indication of capacitor charge.

What's inside

  • SPECIFICATIONS
  • DIMENSIONS
  • TYPICAL APPLICATION
  • DESCRIPTION
  • INSTALLATION
  • ADJUSTMENT
  • TROUBLESHOOTING
  • WARRANTY

Specifications

Nominal input voltage120 VAC (Model 295-120); 240 VAC (Model 295-240)
Input voltage range90-120 VAC (Model 295-120); 190-240 VAC (Model 295-240)
Output voltage170 VDC (Model 295-120); 339 VDC (Model 295-240)
Frequency range50-400 Hz
Operating temperature-20 to +131 F
Humidity tolerance0-97% without condensation
Case material20 gauge CRS
Weight2 lbs

Frequently asked questions

What is the Model 295 Capacitor Trip Device used for?

It is used to trip circuit breakers by using energy stored in a capacitor.

How long can the capacitor hold enough charge to trip the breaker?

It holds sufficient charge for at least 12 seconds after the charging voltage is removed.

Does the device require calibration or adjustment?

No calibration or adjustments are needed.

What should be checked if the device fails to operate?

Check all connections, verify that power is present, and check all fuses.