Installation and setup guide for the Theben CHEOPS 'drive' 310 080 01 electromotor-driven proportional actuator for the European Installation Bus (EIB)…
This one-page guide covers the Theben CHEOPS 'drive' electromotor-driven proportional (constant) actuator, model 310 080 01, which receives set commands from a room temperature regulator and is connected directly to the European Installation Bus (EIB) without a separate bus coupler. The power supply comes from the EIB bus. The document describes the device layout, including the closing cover, the valve opening display, and the program button.
It explains adapter ring selection and assembly/disassembly, bus connection with polarity, use of the two free connection cables as binary inputs for window contacts or presence indicators, entering the physical address with ETS 2, the automatic valve adjustment run, protection against unauthorized removal with the special key and interlock, LED indications of valve setting, and the technical data.
| Power supply | Bus electrical power |
|---|---|
| Permitted operating temperature | 0 °C ... +50 °C |
| Run time | <20 s / mm |
| Set force | >120 N |
| Detection of valve limit stops | Automatic |
| Protection type | EN 60529: IP 21 |
| Dimensions | H x W x D 82 x 50 x 65 mm |
| Included adapter rings fit | Danfoss RA, Heimeier, MNG, Schlösser from 3/93, Honeywell, Braukmann, Dumser, Reich, Landis + Gyr, Oventrop, Herb, Onda |
It is connected directly to the European Installation Bus without any separate bus coupler, and the power supply comes from the EIB.
While it is running one of the three lower LEDs flashes, and the process may last as long as 10 minutes.
The actuator opens to 50 % and displays heating.
Only ETS 2 can be used to assign the physical address and group addresses and to adjust parameters.
They can be used as binary inputs for window contacts and/or presence indicators.