Instruction manual for TERASAKI AR-series Air Circuit Breakers covering safety, installation, operation, OCR settings, maintenance, and troubleshooting.
This document is an instruction manual for the TERASAKI AR-series Air Circuit Breaker (TemPower2). It provides detailed guidelines for installation, operation, and maintenance of air circuit breakers with a draw-out cradle and Type AGR-21B, 22B overcurrent protective devices. The manual covers safety notices, receiving and handling procedures, general information regarding types and circuits, and specific operational instructions.
The permissible operating voltage of the spring charging motor is 85 to 110% of the rated ac voltage or 75 to 110% of the rated dc voltage.
Repeated open/close operation without a pause should not exceed 15 times.
A pause of at least 20 minutes must be provided after 15 repetitions.
The permissible operating voltage is 85 to 110% of the rated AC voltage.