TERASAKI AR-series Air Circuit Breaker Instruction Manual

Instruction manual for TERASAKI AR-series Air Circuit Breakers covering safety, installation, operation, OCR settings, maintenance, and troubleshooting.


TERASAKI AR-series Air Circuit Breaker Instruction Manual - cover page
Brand
TERASAKI
Document type
User Manual
Language
English
Pages
87
File format
PDF
File size
3.2 MB
Published
27 October, 2026
Updated
27 October, 2026
MD5 checksum
FD4FD716F5C46F81AAD7C62C9C43EBC3

About this manual

This document is an instruction manual for the TERASAKI AR-series Air Circuit Breaker (TemPower2). It provides detailed guidelines for installation, operation, and maintenance of air circuit breakers with a draw-out cradle and Type AGR-21B, 22B overcurrent protective devices. The manual covers safety notices, receiving and handling procedures, general information regarding types and circuits, and specific operational instructions.

What's inside

  • SAFETY NOTICES
  • RECEIVING AND HANDLING
  • GENERAL INFORMATION
  • OPERATION
  • OVERCURRENT RELEASE (OCR)
  • MAINTENANCE, INSPECTION AND PARTS REPLACEMENT
  • TROUBLESHOOTING FLOWCHARTS

Frequently asked questions

What voltage range is permissible for the spring charging motor?

The permissible operating voltage of the spring charging motor is 85 to 110% of the rated ac voltage or 75 to 110% of the rated dc voltage.

What is the maximum number of repeated open/close operations allowed by the motor charging mechanism without a pause?

Repeated open/close operation without a pause should not exceed 15 times.

What pause time is required if repeated continuous open/close operation is inevitable?

A pause of at least 20 minutes must be provided after 15 repetitions.

What is the permissible operating voltage range for the spring charging motor in AC voltage?

The permissible operating voltage is 85 to 110% of the rated AC voltage.