The TGBTLE-32/63 series residual current circuit breaker is intended for AC 50 Hz circuits with rated voltage 230V/400V and rated current up to 63A. It cuts off power when human electric shock or grid leakage current exceeds the specified value, and also provides overload and short-circuit protection.
The manual describes classification, normal working and installation conditions, storage conditions, main performance data, outline and mounting dimensions, wiring, common faults and remedies, and ordering information. It also lists installation on a TH35-7.5 (1.0) standard rail, IP20 protection, and specified tightening torques for the copper conductors. This manual is written in Chinese.
| Rated voltage | AC230V/400V |
|---|---|
| Rated current | Up to 63 A |
| Rated residual operating current | 0.015 A, 0.03 A, 0.05 A, 0.075 A, 0.1 A, 0.3 A |
| Rated residual making and breaking capacity (I△m) | 2000 A |
| Protection degree | IP20 |
| Mounting | TH35-7.5 (1.0) standard rail |
| Operating temperature | Upper limit +40 °C, lower limit -5 °C |
| Storage temperature | Upper limit +70 °C, lower limit -40 °C |
| Tightening torque for TGBTLE-32 | 2 Nm |
It is intended for AC 50 Hz circuits with rated voltage 230V/400V and rated current up to 63A.
It states compliance with IEC 61009-1 and GB/T 16917.1.
After a period of operation, generally one month, the test button should be pressed once while the breaker is closed and energized.
The manual says to tighten the copper conductors with a torque of 2 Nm.