Tarkett SureSet Plank and Tile Installation Instructions

Installation instructions for Tarkett SureSet Plank and Tile covering subfloor preparation, moisture testing, and installation requirements.


Tarkett SureSet Plank and Tile Installation Instructions - cover page
Brand
Tarkett
Category
Other
Document type
Installation Guide
Language
English
Pages
11
File format
PDF
File size
215 KB
Published
07 November, 2026
Updated
07 November, 2026
MD5 checksum
14AEDDD38D63D18B96E4E7E9F55DEF55

About this manual

This document provides installation instructions for Tarkett SureSet Plank and Tile flooring. It details requirements for different subfloor types, including suspended, on-grade, and below-grade floors, and specifies the need for a 10mil polyethylene moisture vapor barrier. The guide emphasizes proper site preparation to prevent moisture and alkali transmission from the concrete substrate.

What's inside

  • Subfloors and Underlayments
  • Concrete Floor Requirements
  • Moisture Testing
  • Surface Alkalinity
  • Floor Flatness
  • Painted Floors
  • Radiant Heated Floors

Specifications

Minimum air space for suspended floor18" (460mm)
Recommended moisture vapor barrier10mil polyethylene
Minimum concrete curing time90 days
Maximum moisture emission rate5 lbs./1,000 sq. ft./24 hours
Maximum internal relative humidity80%
Maximum pH reading for concrete9
Maximum operating temperature for radiant floors85ºF (29.4ºC)

Frequently asked questions

What is the minimum curing time for a concrete slab before installation?

A concrete slab shall be cured a minimum of 90 days, preferably 120 days before running moisture tests.

What is the maximum acceptable moisture emission rate for a concrete subfloor?

The results should be no more than 5 lbs. per 1,000 square feet per 24 hours.

Can Tarkett flooring be installed over painted surfaces?

No, Tarkett Inc. does not recommend installation of tile flooring over painted surfaces.

What is the maximum operating temperature for radiant heated floors?

The operating temperature must not exceed 85ºF (29.4ºC).