The manual provides installation, operation, and maintenance instructions for the Taihe An TN3000 fire telephone central.
This document describes the TN3000 fire telephone central designed by Taihe An, covering its features, technical specifications, and system configuration. It includes detailed guidance on installation, wiring, commissioning, and daily maintenance.
The guide also explains basic functions such as calling, conversation, fault alarms, recording management, and menu navigation, helping users operate the system safely and efficiently. This manual is written in Chinese.
| Rated voltage | DC24V (range DC20V~28V) |
|---|---|
| Working current | < 600mA |
| Address capacity | 128 points (1~128) |
| Voice frequency range | 300Hz–3400Hz |
| Crosstalk level | < -60dB |
| Transmission loss | < 5dB |
| Loop resistance | < 300Ω |
| Maximum communication distance | < 1000m |
| Dimensions | 483 mm × 200 mm × 89 mm (L×W×H) |
| Weight | ≈ 3.0 kg |
| Maximum telephone extensions | Up to 100 TN3100 extensions, max 3 simultaneous calls |
| Recording capacity | Up to 9 hours of call recording |
| Information records capacity | 999 records |
| Display | 128×64 dot matrix LCD, 32 Chinese characters |
The TN3000 can connect up to 100 TN3100 telephone extensions, with a maximum of three extensions able to talk simultaneously.
The unit is rated at DC24V, and it operates safely within a voltage range of DC20V to DC28V.
It can operate at temperatures from 0 °C to +40 °C and relative humidity up to 95 % without condensation.
The system supports a communication distance of less than 1000 meters.