The SG1100UD is a modular solar inverter designed for large-scale photovoltaic plants, offering flexible block sizes from 1.1MW to 8.8MW. It supports multiple MPPTs per block and integrates with energy storage systems. The inverter features IP65 protection, DC arc detection, and wireless communication for convenient operation and maintenance.

It is optimized for grid support with fast response times and stable operation under weak grid conditions. The system includes built-in IV diagnosis and PID solutions for enhanced performance and reliability in harsh environments. This manual is written in Chinese.

What's inside

  • Modular Design
  • Electrical Specifications
  • Grid Support Technology
  • Safety and Protection
  • Energy Storage Integration
  • Communication Options
  • Applications and Case Studies

Specifications

Max. Input Voltage1500 V
AC Output Power1100 kVA @40 °C, 1265 kVA @20 °C
Max. AC Output Current1160 A
Rated Grid Voltage630 V
Operating Temperature Range-35 … 60 °C (>40 °C derating)
Degree of ProtectionIP65
Cooling ConceptTemperature controlled forced air cooling
Max. Relative Humidity0 … 100 %, non-condensing
Max. Altitude4000 m (derating > 3000 m)
Communication PortsRS485 / Modbus, Ethernet, Optional: optical fiber

Frequently asked questions

What is the maximum AC output power of the SG1100UD?

1100 kVA at 40°C, 1265 kVA at 20°C.

What is the operating temperature range of the SG1100UD?

-35°C to 60°C, with derating above 40°C.

What communication protocols does the SG1100UD support?

Standard: RS485 / Modbus, Ethernet; Optional: optical fiber.