Installation and maintenance instructions for Spirax Sarco FT, FTB, FTI, OK, FTS-150 and FTS-300IM-2-300-US float and thermostatic steam traps.
This document provides safety, installation, description and operation, and limiting operating condition information for Spirax Sarco float and thermostatic steam traps.
It covers isolation and installation practices, condensate lift pressure, bypass piping, superheat tolerance, and safe handling of cast iron products.
| Superheat tolerance | At least 450°F |
|---|---|
| Surface temperature | May exceed 300°C (572°F) |
| Cold hydraulic test pressure | 1-1/2 times cold PMA |
| Float removal test pressure | Above 600 psi |
| Condensate lift pressure | Approximately 1 psi per 2 ft of lift |
| Bypass line size | At least one pipe size smaller than the trap |
| Maximum operating pressure | Shown on the nameplate |
| Maximum allowable pressure and temperature | Determined by pressure shell design conditions |
Install the trap below the drainage point, in an upright position with the orientation arrow pointing straight down, and protect it with a Spirax Sarco y-pattern strainer.
Bypass piping is not recommended; if a bypass line must be used, it should be at least one pipe size smaller than the trap.
All Spirax Sarco F & T traps will tolerate at least 450°F of temperature.
Sufficient pressure to lift the condensate is approximately 1 psi for each 2 ft of lift.