Installation instructions and troubleshooting guide for the Slant/Fin automatic vent damper used on Galaxy, Sentinel and Sentry series boilers.
This manual provides installation instructions and a troubleshooting guide for the automatic, motorized vent damper designed for Slant/Fin Galaxy, Sentinel and Sentry series gas boilers. It must be left with the owner and hung on or adjacent to the boiler for reference.
The damper increases heating system efficiency by closing the chimney vent when the burner is off and opening it when combustion is required. Installation must conform to the National Fuel Gas Code ANSI Z223.1 and, where required, ASME CSD-1, and the device must be installed by a qualified installer.
| Vent sizes | 4", 5", 6", 7", 8", 9", 10" |
|---|---|
| Wiring voltage | 24VAC |
| Life cycle test | 100,000 trouble-free operations |
| Clearance from combustible materials | 6 inches (152 mm) |
| Certification | CSA retrofit certification ANSI Z21.66 |
Boilers with input under 300,000 Btu/hr must use a vent damper.
It must be installed on the outlet end of the draft hood as close to the draft hood as practicable.
The burner circuit will not be activated.
24VAC, 18 gauge, 90°C wiring is required.