SKUM WAFV-MK2 Water Actuated Foam Valve Data Sheet

Data sheet for the SKUM WAFV-MK2 water actuated foam valve with stainless steel ball valve, actuator pressure range, applications, and ordering information.


SKUM WAFV-MK2 Water Actuated Foam Valve Data Sheet - cover page
Brand
SKUM
Category
Other products
Document type
Datasheet
Language
English
Pages
2
File format
PDF
File size
197 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
95EA5C54BD3C5BC3BEDFD8947D56B49D

About this manual

This data sheet describes the SKUM Water Actuated Foam Valve (WAFV-MK2), which consists of a ball valve and an approved, corrosion-resistant actuator. The valve operates by water pressure only, from the mains water pressure supply on a bladder tank system or from the water motor alarm port in a fire sprinkler system. The valve body is made from 316 stainless steel and the actuator has an anodized aluminum housing. The actuator opens the valve at a water pressure of 2 bar to 16 bar (29 psi to 232 psi) and must be manually reset; it is fitted with a manual override feature.

The WAFV is primarily used in bladder tank foam systems, installed in the foam concentrate line just before the proportioner. It is also used in foam pump balanced pressure proportioning systems and in non-pressurised tank systems where the proportioner is below the tank, preventing foam leakage or foam siphoning into the water line. The document lists features, connections, listings and approvals, ordering information with part numbers for DN 20 to DN 80 sizes, and performance data with dimensions and weights.

What's inside

  • Description
  • Application
  • Listings and Approvals
  • Connections
  • Features
  • Resetting WAFV
  • Ordering Information
  • Performance Data

Specifications

Valve body material316 stainless steel
Actuator housing materialAnodized aluminum
Actuator opening pressure2 bar to 16 bar (29 psi to 232 psi)
Maximum actuator operating pressure12.1 bar (175 psi)
Maximum water or foam pressure through valve12.1 bar (175 psi)
Working temperature-30°C to +100°C
Listings and approvalsPED, ATEX (zone 1), SIL 3
ConnectionsFoam: BSP screw threaded or weld end (WE); water actuating line: BSP 1/4 in.
Valve sizesDN 20, DN 40, DN 50, DN 80

Frequently asked questions

How do I reset the WAFV actuator?

The actuator must be manually reset: check that the resetting lever is attached and can be mounted on the operating shaft, check that pressure from the water actuating line is relieved, then manually operate the lever to close the valve.

What should I do if the actuation pressure exceeds 12.1 bar (175 psi)?

It is recommended that a Pressure Reducing Valve (PRV), PN1327-006, be installed in the actuation line.

Where is the WAFV installed in a bladder tank foam system?

It is installed in the foam concentrate line just before the proportioner; increased water pressure opens the WAFV and discharges foam concentrate to the proportioner.

Can the WAFV be used with all types of foam concentrates?

Yes, the document states that a WAFV may be used with all types of foam concentrates.