SKK DSV-HC / DSV-S Automatic Tank Gauging System Product Leaflet

Product leaflet for the SKK DSV-HC / DSV-S automatic tank gauging system, covering up to eight tanks, alarms and a thermal printer.


SKK DSV-HC / DSV-S Automatic Tank Gauging System Product Leaflet - cover page
Brand
SKK
Category
Monitoring Equipment
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
10.9 MB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
2EE627BE6009B45BD91DC501ED9BEFBD

About this manual

The SKK DSV automatic tank gauging system consists of the DSV-HC digital console unit and DSV-S level meters installed above underground tanks. The leaflet says the system can measure up to eight tanks by the voltage method, with precision less than +1% compared with total volume, and lists petrol, diesel, kerosene, heavy oil, waste oil and other liquids as measurable.

Listed features include a 7-segment LED volume indicator, bar graph indication for all tanks, high/low warnings with buzzer, blinking bar graph and non-voltage contactor, abnormal/delivery confirmation warnings, and a thermal printer. The system also lists SS-LAN POS communication, intrinsically safe explosion-proof construction (IA2G4), AC 100–240 V power, and installation of the console indoors in a non-hazardous area with the level meter in the hazardous area above the tank.

What's inside

  • Model
  • Number of measurable tank
  • Measurement Method
  • Precision
  • Measurable Liquid
  • Indicator
  • High/Low Warning
  • Printer
  • POS Communication
  • Explosion Proof Structure

Specifications

ModelDSV-HC (Digital Console unit) / DSV-S (Level meter above tank)
Number of measurable tanksUp to 8 tanks
Measurement methodVoltage method
PrecisionLess than +1% compared with total volume
Measurable liquidsPetrol, diesel, kerosene, heavy oil, waste oil and other liquids
Volume indicator7-segment LED, 5 digits
Bar graph indicatorSimultaneous indication for all tanks
High/low warningBuzzer / bar graph blinking / non-voltage contactor
PrinterThermal type
POS communicationSS-LAN
Explosion-proof structureIntrinsically safe explosion-proof structure IA2G4
Power supplyAC 100–240 V, 50/60 Hz
Power consumptionLess than 25 VA without optional equipment
Area of installationDigital console: indoor non-hazardous area; level meter: hazardous area above tank
Operating temperatureDigital console: 0 to +40°C without dew condensation; level meter: -2 to +40°C
DimensionsDigital console: 323 (H) x 230 (W) x 70 (D); level meter: 114 (H) x 180 (W) x 162 (D)

Frequently asked questions

How many tanks can the SKK DSV system measure?

It can measure up to eight tanks.

What liquids can the SKK DSV system measure?

Petrol, diesel, kerosene, heavy oil, waste oil and other liquids.

What is the measurement precision?

Less than +1% compared with total volume.

What power supply does the system use?

AC 100–240 V, 50/60 Hz, with power consumption less than 25 VA without optional equipment.