About this manual

The Siri SR-HJWSK system is an environmental management solution for outdoor electrical cabinets and transformer substations. It prevents condensation and icing by monitoring temperature, humidity, and dew point to control heating films, dehumidifiers, and fans. The system consists of a main unit, heating films, and micro dehumidifiers. This manual is written in Chinese.

What's inside

  • Overview
  • Unboxing Inspection
  • Safety Precautions
  • Technical Specifications
  • Product Panel Diagram
  • Wiring Diagram
  • Installation Dimensions
  • Working Principle
  • Troubleshooting

Specifications

Power SupplyAC/DC 85 ~ 265V
Operating Temperature-40℃ ~ 70℃
Altitude< 4000m
Power Consumption≤ 15W (without load)
Temperature Control Range-40℃ ~ 80℃
Temperature Accuracy1.0 Grade
Humidity Control Range20%RH ~ 99%RH
Humidity Accuracy± 3%RH
Relay Contact Capacity5A, 250VAC / 5A, DC30V
RS485 Communication4800bps/9600bps
Max Communication Distance1000m
Cutout Size147mm x 69mm
Design Life> 15 years

Frequently asked questions

What is the purpose of the SR-HJWSK system?

It prevents condensation and icing in transformer cabinets by controlling heating films, dehumidifiers, and fans based on environmental conditions.

What sensors are included in the unboxing list?

The package includes environmental temperature/humidity sensors, dew point collectors, smoke detectors, oil temperature sensors, and dehumidifiers.

What safety precaution is required during high voltage testing?

You must disconnect the sensor plugs from the device before performing voltage withstand tests.

What is the cutout size for panel installation?

The required cutout size for the panel is 147mm x 69mm.