User manual for the Shandong Kexin Dianqi CSMS-B100 series surge protector, including specifications, installation, and technical parameters.
The CSMS-B100 series surge protector from Shandong Kexin Dianqi is designed according to GB18802.1 and IEC61643-1 for AC 50 Hz systems at 220 V/380 V and below, including TN-S, TN-C-S, TT, and IT systems. Each module has a nominal discharge current of 60 kA and a maximum discharge current of 100 kA (8/20 μs), and the device is intended for Type II lightning protection at LPZ2 or the LPZ2/LPZ3 boundary.
Features include quality surge components, overcurrent and thermal protection, low leakage current, fast response, low residual voltage, and a pluggable modular design that can be replaced without de-energizing. Installation uses a 35 mm DIN rail; the manual also gives wiring, grounding, fault indication, dimensions, environmental limits, and a 3-year product warranty. This manual is written in Chinese.
| SPD model | CSMS-B100/AC385-4P |
|---|---|
| Rated voltage (Un) | 220 V/380 V |
| Maximum continuous operating voltage (Uc) | 385 V/50 Hz |
| Nominal discharge current (In, 8/20 μs) | 60 kA |
| Maximum discharge current (Imax, 8/20 μs) | 100 kA |
| Voltage protection level (Up) | ≤2.4 kV |
| Response time | ≤25 ns |
| Leakage current | ≤15 μA |
| Poles | 1P, 2P, 3P, 4P (optional) |
| Dimensions (W×H×D) | 108×90×62 mm |
| Operating temperature | -40 °C to +80 °C |
| Protection rating | IP20 |
| Installation | 35 mm standard DIN rail |
| Product warranty | 3 years |
It is designed according to GB18802.1 and IEC61643-1.
The nominal discharge current is 60 kA and the maximum discharge current is 100 kA (8/20 μs).
Replace it when the module fault indicator window shows red.
The grounding resistance should be less than 10 Ω.