Operating instructions for the Setra Systems Model 206 Industrial Pressure Transducer, covering installation, electrical wiring, calibration, and return…
This document provides operating instructions for the Setra Systems Model 206 Industrial Pressure Transducer. It details the device's ability to sense gauge and vacuum pressure, converting it to a proportional high-level analog output. The manual covers two standard versions: 9 to 30 VDC with 4 to 20 mA output, and 12 to 28 VDC with 0.1 to 5.1 VDC output.
| Excitation Voltage | 9 to 30 VDC or 12 to 28 VDC |
|---|---|
| Output Current | 4 to 20 mA |
| Output Voltage | 0.1 to 5.1 VDC |
| Operating Temperature | -40° to +260°F (-40 to +127°C) |
| Compensated Temperature | -20 to +80°C |
| Media Compatibility | 17-4 PH stainless steel |
| Factory Calibration Load | 50 KΩ |
| Current Output Load | 0-800 Ω |
The transducers are designed to be used with any gases or liquids compatible with 17-4 PH stainless steel.
The shield should be connected to the system's loop circuit ground to improve electrical noise rejection.
No, every model 206 is factory calibrated and should require no field adjustment.
The warranty is one year from the date of sale, covering defects in materials or workmanship.