Operating instructions for the Selec MFM384-R-C multifunction energy meter covering specifications, wiring, configuration, and Modbus communication.
The Selec MFM384-R-C is a DIN-rail mounted multifunction energy meter with a backlit LCD display showing electrical parameters. It supports multiple wiring configurations (3-phase 4-wire, 3-phase 3-wire, single-phase 2-wire) and provides measurement of voltage, current, power, energy, power factor, and frequency with accuracy classes up to 0.5% of full range.
The meter features RS485 Modbus RTU communication with programmable baud rates (300 to 19200 bps), configurable CT/PT ratios, password-protected configuration via front-panel keys, and energy reset functions. It operates on 85-270V AC supply, consumes less than 8 VA, and is rated for indoor use up to 2000 m altitude with an operating temperature range of -5°C to 60°C.
| Display | Liquid crystal display with backlight, 1 line 4 digits and 2 lines 7 digits per line |
|---|---|
| Wiring Configurations | 3Ø4 wire, 1Ø2 wire, 3Ø3 wire, 2Ø-3 wire |
| Rated Input Voltage | 11 to 300V AC (L-N); 19 to 519V AC (L-L) |
| Rated Input Current | Nominal 5A AC (Min 1mA, Max 6A) |
| Frequency Range | 45-65 Hz |
| CT Primary Range | 1A/5A to 10,000A (programmable) |
| CT Secondary | 1A or 5A (programmable) |
| PT Primary Range | 100V to 500kV (programmable) |
| PT Secondary Range | 100V to 500V (programmable) |
| Power Consumption | Less than 8 VA |
| Operating Temperature | -5°C to 60°C |
| Storage Temperature | -20°C to 75°C |
| Mounting | DIN rail mounting |
| Weight | 208 g |
| Communication Interface | RS485 Modbus RTU |
| Baud Rates | 300, 600, 1200, 2400, 4800, 9600, 19200 bps |
| Transmission Distance | 500 meters maximum |
| Measurement Accuracy (Voltage) | ±0.5% of full range |
| Measurement Accuracy (Current) | ±0.5% of full range |
| Measurement Accuracy (Active Power) | ±1.0% of full range |
| Measurement Accuracy (Power Factor) | ±0.01 of full range |
The meter supports 3-phase 4-wire, 1-phase 2-wire, 3-phase 3-wire, and 2-phase 3-wire configurations.
The rated input voltage is 11 to 300V AC line-to-neutral and 19 to 519V AC line-to-line.
Press the PAGE and PRG keys simultaneously for 3 seconds to enter or exit configuration mode.
The meter supports baud rates of 300, 600, 1200, 2400, 4800, 9600, and 19200 bps.