Schroeder SCH-OWT Oil-Water Mixture Transmitter Controller Product Leaflet

The Schroeder SCH-OWT oil-water mixture transmitter controller measures water content in non-water-soluble oils by capacitance, with LED display, 4–20 mA…


Schroeder SCH-OWT Oil-Water Mixture Transmitter Controller Product Leaflet - cover page
Brand
Schroeder
Category
Monitoring Equipment
Document type
Product Leaflet
Language
Chinese
Pages
3
File format
PDF
File size
377 KB
Published
19 November, 2026
Updated
19 November, 2026
MD5 checksum
5A07ABB995B184DCDBED2817F0F24D2A

About this manual

The Schroeder SCH-OWT oil-water mixture transmitter controller is an industrial instrument for precisely measuring the water content of non-water-soluble oils such as turbine oil. It uses a capacitance measuring principle: the dielectric constant between the capacitor plates changes when water mixes with the oil, changing the capacitance, which a microcircuit processes to show the water percentage in real time.

It provides a 4-digit LED real-time display, one 4–20 mA analog output corresponding to the range (maximum load 500 Ω), and two settable SPDT alarm contacts. Power supply is DC24V or optional AC/DC220V; the unit supports field calibration in LIN (linear) or POT (ten-segment) modes and has an IP67 protection rating. This manual is written in Chinese.

What's inside

  • Working Principle
  • Overview
  • Technical Parameters
  • Features
  • Wiring Terminal Diagram
  • Field Calibration
  • Appearance Dimensions and Wiring Terminal Diagram
  • Selection Table
  • Ordering Information

Specifications

Power supplyDC24V, AC/DC220V optional
Measurement range0–10%, field settable
Analog output4–20 mA, maximum load 500 Ω
Alarm output2 settable SPDT contacts
Resolutionnot greater than 0.03%
Operating temperature0–70°C
Process pressure1.6 MPa
Protection classIP67

Frequently asked questions

What is the measuring range of the Schroeder SCH-OWT?

0–10%, and it can be set on site.

What output signals does the SCH-OWT provide?

One 4–20 mA analog signal and two pairs of alarm contact signals.

What power supply options are available?

DC24V, with AC/DC220V optional.

What is the protection rating of the controller?

IP67.