Rikenkeiki SD-1DRI Gas Detector Section User Manual

This manual covers the operation, installation, maintenance, and specifications of the Rikenkeiki SD-1DRI gas detector section for combustible gases.


Rikenkeiki SD-1DRI Gas Detector Section User Manual - cover page
Brand
Riken Keiki
Category
Other Electronics
Document type
User Manual
Language
Japanese
Pages
69
File format
PDF
File size
4.8 MB
Published
12 October, 2026
Updated
12 October, 2026
MD5 checksum
9B916E3E861A5FF9CE70B936D69A7093

About this manual

The Rikenkeiki SD-1DRI is a built-in signal converter gas detector section designed to detect combustible gases in the atmosphere. It functions as a safety instrument by issuing alarms when dangerous concentrations are detected, rather than serving as an analytical device for quantitative measurement.

This manual provides comprehensive instructions on installation, wiring, and operation procedures. It details various alarm actions, maintenance checks including zero adjustment and calibration methods, storage guidelines, troubleshooting steps, and technical specifications for both Japanese and export models. This manual is written in Japanese.

What's inside

  • Product Overview
  • Safety Important Matters
  • System Design Considerations
  • Installation Method
  • Operation Methods
  • Gas Alarm Actions
  • Maintenance Checks
  • Calibration Methods
  • Troubleshooting
  • Product Specifications

Specifications

Detection PrincipleNon-dispersive infrared absorption type
Target GasCombustible gas
Detection MethodSuction type (via external unit)
Inlet Flow Rate1.0 ±0.1L/min
Power SupplyDC24V ±10%
Output SignalDC4 ~20mA (Linear)
Transmission DistanceUp to 1.25km or 2.0km depending on cable size
Power ConsumptionMax 2W

Frequently asked questions

Is the SD-1DRI an analytical instrument?

No, it is a safety instrument designed to detect combustible gases and issue alarms, not for quantitative or qualitative analysis.

How often should zero adjustment be performed?

Zero adjustment using ambient air should be performed regularly, approximately once a month.

What is the response time for the gas alarm?

The instrument provides an alarm within 30 seconds when exposed to a gas concentration providing 1.6 times the set value.

Does the alarm reset automatically?

Yes, the gas alarm action is designed to recover automatically once the hazardous condition clears.