Product leaflet for the Richang Dianqi RCG6-40.5 series 40.5 kV SF6 gas-insulated switchgear (C-GIS), covering features, environment and technical parameters.
The RCG6-40.5 series SF6 gas-insulated switchgear (C-GIS) is a switchgear product developed by Richang Dianqi (日昌电气). It uses low-pressure SF6 gas as the insulating medium, with a vacuum circuit breaker and a three-position switch as the main primary components, sealed inside a gas-filled compartment made of 3 mm thick stainless steel plate welding. It is a complete AC 50 Hz distribution device for single busbar and single busbar sectionalized systems at 40.5 kV.
The document describes the product's features, applicable standards, service environment, core gas tank unit and components such as the VRC-40.5/T circuit breaker and SRC-40.5/T direct-acting three-position switch, factory inspection items, and a main technical parameter table. Stated applications include power generation companies, small and medium generator power transmission, industrial and mining enterprise distribution, substation receiving and sending, and starting of large high-voltage motors. This manual is written in Chinese.
| Rated voltage | 40.5 kV |
|---|---|
| Rated frequency | 50 Hz |
| Rated current | 1250 / 2500 A |
| Power-frequency withstand voltage (phase-to-phase, to earth, 1 min) | 95 kV |
| Lightning impulse withstand voltage (phase-to-phase, to earth) | 185 kV |
| Rated short-time withstand current | 25 kA (21.8) / 31.5 kA (27.4) |
| Rated peak withstand current | 63 kA (54.8) / 80 kA (69.6) |
| Rated short-circuit breaking current | 25 / 31.5 kA |
| Rated short-circuit making current | 63 / 80 kA |
| Rated filling pressure | 0.02 MPa |
| Annual gas leakage rate | <0.01% |
| Mechanical life (circuit breaker) | 20000 operations |
| Protection rating | Enclosure IP41, gas compartment IP67 |
| Auxiliary/control circuit rated voltage | DC 110/220 V, AC 110/220 V |
| Loss of service continuity category | LSC2B |
The gas tank is 100% leak-tested after assembly and gas filling, and the annual relative gas leakage rate is below 0.01%.
The gas tank reaches IP67, so its interior is unaffected by the external environment and it has short-term flood resistance and anti-condensation capability.
It can be used at altitudes up to 4000 m; above 1000 m the filling pressure must be specially adjusted during manufacture, so this should be noted when ordering.
The SRC-40.5/T direct-acting three-position switch provides working, isolating and earthing functions, with mechanical and electrical interlocks to prevent misoperation.