RENLE RM200/RM100 intelligent motor protector series leaflet: motor protection functions, starting control modes, monitoring data, CTs and wiring terminals.
This leaflet presents the RENLE RM200/RM100 series intelligent motor protector (also written M200/M100), described by Shanghai RENLE Technology as a microprocessor-based motor intelligent management system. It explains how motor operation data is collected, how alarm and trip levels with delay times are set, and how protection information is sent through a communication interface to a host computer. Models are divided into M200 (full functions) and M100 (a simplified version with partial protection functions), and by protocol into -M (Modbus) and -P (Profibus).
The brochure lists the motor protection functions, the motor starting control modes integrated in the device, and the operating data that can be monitored, including three-phase current and voltage, power factor, active power, energy, leakage current and frequency. It also covers the operating panel DS, the built-in 0.5-63A current transformer and optional external transformers, the zero-sequence current transformer for leakage measurement, the terminal arrangement of X1 to X4, the host dimensions and TS35 rail mounting. This manual is written in Chinese.
| Built-in current transformer range | 0.5-63 A primary side |
|---|---|
| Motor rated current range with built-in CTs | 0-63 A (external CTs above 63 A) |
| External transformer ratings | 200A (63A-200A), 300A (200A-300A), 400A (300A-400A), 500A (400A-500A), 800A (500A-800A) |
| External transformer secondary current | 1 A |
| Zero-sequence current transformer sizes | Ø45, Ø80, Ø100 |
| Host mounting | TS35 DIN rail, terminals facing up |
| Power supply terminals | 220 Vac |
| Programmable relay outputs | 5 A 220 Vac |
| Communication terminals | RS485 |
| Voltage input terminals | 220 Vac |
The M200 offers full functions, while the M100 is a simplified version of the M200 with only part of the protection functions.
Models ending in -M use Modbus and models ending in -P use Profibus.
The built-in transformers are allowed for motor rated currents of 0-63 A; when the motor current is greater than 63 A an external current transformer is used.
Automatic reset, remote reset and local reset.
It is mounted on a TS35 DIN rail with the terminal side facing up.